NFS2-3030 Intelligent Addressable Fire Alarm Control Panel

Features

  • Certified for seismic applications when used with the appropriate
    seismic mounting kit.
  • Approved for Marine applications when a marine-listed version is
    used with marine-listed compatible equipment. See DN-60688.
  • Complies with UL 2572 Mass Notification Systems (NFS2-3030
    version 20 or higher).
  • One to ten isolated intelligent Signaling Line Circuits (SLC) Class
    A, B, or X.
  • Wireless fire protection using SWIFT Smart Wireless Integrated
    Fire Technology. See DN-60820.
  • Up to 159 detectors and 159 modules per SLC; 318 devices per
    loop/3,180 per FACP or network node.
    – Detectors can be any mix of photo, thermal, or multi-sensor;
    wireless detectors are available for use with the FWSG(A).
    – Modules include addressable pull stations, normally open contact devices, two-wire smoke detectors, notification, or relay;
    wireless modules are available for use with the FWSG(A).
  • Large 16 line, 640 character LCD backlit display or use displayless as a network node.
  • Network options:
    – High-speed network for up to 200 nodes (N16e/x, NFS2-3030,
    NFS2-640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM,
    ONYXWorks, NFS-3030, NFS-640, and NCA).
    – Standard network for up to 103 nodes (N16e/x, NFS2-3030,
    NFS2-640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM,
    ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP300/400, AFP-1010, and AM2020). Up to 54 nodes when DVCEM is used in network paging.
  • Built-in Alarm, Trouble, Security, and Supervisory relays.
  • VeriFire® Tools online/offline program option.

 

NFS2-3030 Intelligent Addressable Fire Alarm Control Panel