NFS-320 Intelligent Addressable Fire Alarm Control Panel

Features

  • Certified for seismic applications when used with the appropriate
    seismic mounting kit.
  • Approved for Marine applications when used with listed compatible equipment. See DN-60688
  • One isolated intelligent Signaling Line Circuit (SLC) Class A, B,
    or X.
  • Wireless fire protection using SWIFT Smart Wireless Integrated
    Fire Technology. See DN-60820.
  • Up to 159 detectors and 159 modules per SLC; 318 devices maximum.
    – Detectors can be any mix of photo, thermal, or multi-sensor;
    wireless detectors are available for use with the FWSG(A).
    – Modules include addressable pull stations, normally open contact devices, two-wire smoke detectors, notification, or relay;
    wireless modules are available for use with the FWSG(A).
  • Standard 80-character display.
  • Network options:
    – High-speed network for up to 200 nodes (N16e/x, NFS2-3030,
    NFS2-640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM,
    ONYXWorks, NFS-3030, NFS-640, and NCA).
    – Standard network for up to 103 nodes (N16e/x, NFS2-3030,
    NFS2-640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM,
    ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP300/400, AFP-1010, and AM2020). Up to 54 nodes when DVCEM is used in network paging.
  • 6.0 A power supply with four Class A/B built-in Notification Appliance Circuits (NAC). Selectable System Sensor, Wheelock, or
    Gentex strobe synchronization.
  • Built-in Alarm, Trouble, Security, and Supervisory relays.
  • VeriFire® Tools online or offline programming utility. Upload/
    Download, save, store, check, compare, and simulate panel databases. Upgrade panel firmware.
  • Autoprogramming and Walk Test reports.

Intelligent-Addressable